Heavy Duty Binary / Gray Output Converter NCV-30H
Description
NCV-30H is digital binary or gray code output converter which is connecting with heavy duty ABSOCODER position sensors
Model coding
NCV-30H[1][2][3]
- [1]Output code
-
Code Output code B Binary G Gray
- [2]Output system
-
Code Output system N Sink type
- [3]Applicable sensor
-
Code Applicable sensor LC CYLNUC,Inrodsensor(IRS-51.2P) L8 VLS-8SM Note) Binary code is only available for L8.
ABSOCODER Basic Configuration
Specification
General specification
Item | Specification |
---|---|
Power supply voltage | 24VDC±10% (including ripple) |
Power consumption | 10W or less |
Insulation resistance | 20MΩ or more between external DC power terminals and ground (by 500 VDC insulation resistance tester) |
Withstand voltage | 500 VAC, 60Hz for 1 minute between external DC power terminals and ground |
Vibration resistance | 20m/s2 10〜500Hz, 10cycles of 5 minutes in 3 directions, conforms to JIS C 0040 standard |
Ambient operating temperature | 0 ~ +55℃ (No freezing) (Surrounding air temperature rating of 55℃ maximum) |
Ambient operating humidity | 20 ~ 90 %RH (No condensation) |
Ambient operating environment | Free from corrosive gases and excessive dust |
Ambient storage temperature | -10〜+70℃ |
Grounding | Must be securely grounded (ground resistance of 100 ohm or less) |
Construction | Book-shelf type within enclosure, DIN rail mountable |
Outside dimension (mm) | 39(W)×155(H)×93(D) Refer to dimensions for details. |
Mass | Approx. 0.4kg |
Performance Specification
Item | Specification | ||
---|---|---|---|
Converter model | NCV-30HBNLC, NCV-30HGNLC, NCV-30HBNL8 | ||
Number of detection axes | 1 | ||
Position data sampling tim |
0.2ms | ||
Status output signal | Latch pulse (Position data reading timing) : 1 point System ready : 1 point |
||
Input signals | Position data hold signal : 1 point Zero point setting signal : 1 point Error clear signal : 1 point |
||
Front panel function | Zero point setting, error clear | ||
Switch (on rear face of product) |
Position data increase/decrease direction setting (CW / CCW) : 1point | ||
Position data update cycle | High-speed | 0.2ms | |
0.4ms | |||
0.8ms | |||
1.6ms | |||
3.2ms | |||
Low-speed | 12.8ms | ||
25.6ms | |||
51.2ms | |||
HOLD signal format | Transparent format | ||
PC synchro format | |||
Position data output format | Binary code output | ||
Sign magnitude code | |||
Minus zone "0" output | |||
Monitor LED | Output state monitor | Position data output, latch pulse output | |
Input state monitor | HOLD input, zero point setting input, error clear input | ||
Error state monitor | Sensor disconnected error, sensor data error, memory error, low power error, -5V power supply error, LPA error |
Number of divisions, resolution, and sensor cable length of the ABSOCODER sensor
CYLNUC Smart Linear Position Sensing Cylinder
Item | Specification | |
---|---|---|
Converter model | NCV-30HBNLC, NCV-30HGNLC | |
Applicable sensor | CYLNUC | |
Absolute detection range | 12.8mm | |
Resolution | 1.5625μm | |
Position detection format | Semi - absolute position detection | |
Max. sensor cable length | Standard(S) | 200m |
Robotic (RBT) | 100m | |
JKPEV-S (1.25mm2×5P) |
200m |
General Purpose Inrodsensor
Item | Specification | |
---|---|---|
Converter model | NCV-30HBNLC, NCV-30HGNLC | |
Applicable sensor | IRS-51.2P | |
Absolute detection range | 51.2mm | |
Resolution | 6.25μm | |
Position detection format | Semi - absolute position detection | |
Max. sensor cable length | Standard(S) | 200m |
Robotic (RBT) | 100m | |
JKPEV-S (1.25mm2×5P) |
200m |
VLS Linear type
Item | Specification | |
---|---|---|
Converter model | NCV-30HBNL8 | |
Applicable sensor | VLS-8SM | |
Absolute detection range | 8.192mm | |
Resolution | 1μm | |
Position detection format | Semi - absolute position detection | |
Max. sensor cable length | Standard(S) | 200m |
Robotic (RBT) | 100m | |
JKPEV-S (1.25mm2×5P) |
- |
I/O spcification
Item | Specification | |
---|---|---|
Converter model | NCV-30HBNLC, NCV-30NGNLC, NCV-30HBNL8 | |
Input | Input signals | HD (Position data HOLD) : 1 point ZPS (Zero point setting signal) : 1 point CLR (Error clear signal) : 1 point |
Input circuit | DC input, photo-coupler isolation | |
Input logic | Negative logic | |
Rated input voltage | 12 ~ 24VDC (10 ~ 27VDC) | |
Rated input current | 10mA (24VDC) | |
ON voltage | 10VDC or more | |
OFF voltage | 4VDC or less | |
Output | Output signals | D0〜D23 (Position data) : 24 points NOR (System Ready) : 1 point LP (Position data reading timing): 1 point |
Output circuit | Open drain sink output, photo-coupler isolation | |
Output logic | Negative logic | |
Rated load voltage | 12 ~ 24VDC (30VDC max.) | |
Max. load current | 50mA | |
Max. voltage drop when ON | 0.8 V or less |